Saukewa: PAC900S12-B2

AC zuwa DC Power Supply HVDC-DC Module

PAC900S12-B2 yana goyan bayan shigar AC na 90V zuwa 264V da shigarwar HVDC na 180V zuwa 300V.
PSU tana ba da fitarwa ɗaya kuma tana goyan bayan hanyoyin fitarwa guda uku MV12, SV12 da MV6.


Linkedin
43f45020
384b0 ku
754c4db4
6ec95a4a

Cikakken Bayani

Tags samfurin

Ƙarfin fitarwa da aka ƙididdige shi ne 900 W. PSU yana da zafi swappable, daidaita halin yanzu, kuma yana goyan bayan haɗin 1+1 ko 2+2.
PSU tana goyan bayan sadarwar PMBus, kuma tana aika bayanan PSU zuwa tsarin don sauƙaƙe kulawa da gudanarwa.

Siffofin
● fficc 94% (Vin = 230 V AC, Pout = 450 W, TA = 25 ° C, ba tare da fan)
● Zurfin x Nisa x Tsawo: 183.0 mm x 68.0 mm x40.5 mm
● Wutar lantarki: 110 V AC / 220 V AC guda-lokaci, 240 VDC
● Yana goyan bayan kariyar shigar AC don ƙarancin ƙarfin lantarki, yawan ƙarfin wuta,
overcurrent, short circuit, da kuma PFC overvoltage
● Yana goyan bayan kariyar shigarwar HVDC don wuce gona da iri, rashin ƙarfi, da yawan ƙarfin PFC
● Yana goyan bayan kariyar fitarwa don wuce gona da iri, wuce gona da iri, gajeriyar kewayawa, da zafin jiki
● I2C don sarrafawa, shirye-shirye, da saka idanu
● CE, UL, TUV, CCC, BSMI, BIS cfic da rahoton CB akwai
● 80 Plus platinum makamashi fficc cfic
● IEC 60950-1, EN 60950-1, UL 60950-1, GB 4943.1, IEC 62368-1
● Mai yarda da RoHS
Aikace-aikace: Server
PSU na iya jure wa ƙarfin shigarwa na 318 V AC na tsawon sa'o'i 48 (an yarda da yanayin da ba aiki ba).
Inrush halin yanzu ya kamata ya dace da buƙatun a cikin ETSI EN 300 132-3.
Lokacin gwada matsakaicin shigarwa na halin yanzu, tabbatar da cewa ƙarfin lantarki na tashar shigar da wutar lantarki ya cika abin da ake buƙata kuma abin da ake fitarwa shine 900 W.
Bukatun ƙira na Raba na Yanzu
1. Yana goyan bayan yanayin 1+1 ko 2+2. Rabawa na yanzu kawai a cikin yanayin MV12.
2. Jimlar kaya a farawa a cikin yanayin aiki daidai gwargwado ya kamata ya zama ƙasa da ƙimar ƙimar PSU ɗaya.
3. Lokacin da PSUs ke aiki a yanayin 1+1 ko 2+2, idan ɗayan PSU yana aiki a yanayin MV6 kuma sauran PSUs suna aiki a yanayin MV12, PSUs yakamata suyi aiki yadda yakamata ba tare da ffc juna ba.
4. A cikin yanayin da ba a shigar da ff PSUs tare, siginar I-MON na PSUs guda biyu bai kamata ffc aikin PSU na yau da kullun ba lokacin da aka haɗa su kai tsaye.
5. Rashin daidaituwa na rabawa na yanzu kawai a yanayin yanayin zafi na al'ada.








  • Na baya: